Commercial Make-Up Air Unit (MUA) Hydronic Freeze Stat Lockout & Glycol Pre-Heat Coil Rupture: Capillary Bulb Failure, Front Range Sub-Zero Shock & ASME Brazing Repair

At five o’clock on a freezing January morning along the Colorado Front Range, a brutal Arctic cold front drives outdoor temperatures down to minus eighteen degrees Fahrenheit (-18°F) across Broomfield. Inside a high-volume commercial hotel kitchen, flagship restaurant, or corporate campus cafeteria, the morning prep shift arrives.

The kitchen staff fires up the commercial exhaust hoods.

Ten thousand cubic feet per minute (10,000 CFM) of air starts pulling through the grease filters.

Up on the rooftop, the commercial Make-Up Air Unit (MUA) kicks into high gear to replace the exhausted air.

Its motorized outside air dampers open wide, drawing a massive gale of sub-zero Colorado air directly into the intake plenum.

Suddenly, an ominous banging echoes through the roof ductwork.

Within three minutes, a deluge of boiling, chemical-smelling pink water punches through the kitchen acoustic ceiling tiles.

Water is cascading across commercial gas ranges, deep fryers, and electrical prep stations.

The MUA hydronic pre-heat coil has suffered a catastrophic **Freeze-Thaw Rupture**.

Every linear inch of the multi-row copper finned tube bundle has split wide open under forty thousand pounds of internal ice expansion pressure.

This is not an ordinary heating glitch.

It is an immediate commercial facility shutdown involving **NFPA 96 ventilation mandates, International Mechanical Code (IMC) Chapter 5 compliance**, structural electrical flooding, and thousands of dollars in contaminated glycol loss.

Let’s examine the thermodynamics of sub-zero make-up air ventilation, calculate log mean temperature differentials across hydronic coils, analyze capillary freeze stat mechanics, evaluate ice expansion hoop stress, and detail master plumber ASME silver brazing and emergency bypass protocols across the Colorado Front Range.

Commercial rooftop makeup air unit hydronic pre-heat coil freeze stat burst in Broomfield Colorado
Figure 1: Commercial rooftop make-up air unit (MUA) hydronic pre-heat coil assembly showing copper tube U-bends, capillary freeze stat switch, and isolation valves in Broomfield, Colorado.

1. The Mechanical Engineering of Make-Up Air Units: NFPA 96 & IMC Chapter 5

Why do commercial kitchens and industrial facilities require Make-Up Air Units (MUAs)?

Under **International Mechanical Code (IMC) Section 508 and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations)**, commercial kitchen exhaust hoods pull immense volumes of air out of the building to capture grease vapor, carbon monoxide, and cooking heat.

A typical commercial restaurant exhaust system exhausts between **4,000 to 15,000 CFM**.

If a commercial building exhausts ten thousand cubic feet of air every minute without replacing it, intense negative building pressure develops.

Doors become impossible to open. Water heater flues back-draft lethal carbon monoxide into dining rooms. Kitchen grease hoods fail to capture smoke.

To prevent this, the Make-Up Air Unit (MUA) is interlocked with the exhaust hood fans.

Whenever the exhaust fans energize, the MUA must introduce **100% outside air**, pre-conditioned to a comfortable delivery temperature between **65°F and 72°F**.

The Sub-Zero Front Range Thermal Challenge

In Colorado, the incoming outdoor air is not mild.

During winter polar vortex events, outdoor air enters the rooftop intake at **-10°F to -25°F**.

To heat 10,000 CFM of air from -15°F to +70°F requires an enormous thermal heating capacity:

$$q = 1.08 \cdot CFM \cdot \Delta T = 1.08 \cdot 10,000 \cdot (70 – (-15)) = 1.08 \cdot 10,000 \cdot 85 = 918,000 \text{ BTU/hr}$$

That is nearly **one million BTUs per hour** transferred through a multi-row copper hydronic coil measuring just six feet by four feet.

Outdoor Temp ($T_{\text{in}}$) Target Delivery Temp ($T_{\text{out}}$) CFM Airflow Volume Hydronic Heat Duty (BTU/hr) Glycol Flow Required (50% Mix at 160°F)
35°F (Mild Winter) 70°F 10,000 CFM 378,000 BTU/hr 42.0 GPM
10°F (Standard Freeze) 70°F 10,000 CFM 648,000 BTU/hr 72.0 GPM
-10°F (Severe Cold Front) 70°F 10,000 CFM 864,000 BTU/hr 96.0 GPM
-25°F (Polar Vortex Shock) 70°F 10,000 CFM 1,026,000 BTU/hr 114.0 GPM

Look closely at the data table above.

When temperatures plummet to -25°F, the required heat-transfer fluid flow rate spikes to **114 Gallons Per Minute (GPM)**.

If the hydronic circulating pump suffers even a thirty-second power dip, or if an automated two-way modulating control valve throttles back because the kitchen gets warm, fluid velocity drops inside the copper tubes.

At -20°F incoming air velocity, static water freezes inside a 5/8-inch copper tube in **less than forty-five seconds**.

2. The Thermodynamics of Coil Heat Transfer: LMTD & Air Stratification

How does incoming Arctic air freeze a heating coil while hot water is actively flowing through it?

The answer lies in **Thermal Air Stratification and Log Mean Temperature Difference (LMTD)**.

Heat transfer across the multi-row finned copper coil is calculated using the governing formula:

$$q = U \cdot A \cdot \Delta T_{\text{lm}}$$

Where:

  • $q$ = Total thermal energy transfer rate ($BTU/hr$)
  • $U$ = Overall heat transfer coefficient of the aluminum-finned copper bundle ($BTU/(hr\cdot ft^2\cdot^\circ F)$)
  • $A$ = Exterior surface area of the finned heat exchanger ($ft^2$)
  • $\Delta T_{\text{lm}}$ = Log Mean Temperature Difference across counter-flow fluid circuits
$$\Delta T_{\text{lm}} = \frac{(T_{\text{fluid,in}} – T_{\text{air,out}}) – (T_{\text{fluid,out}} – T_{\text{air,in}})}{\ln\left(\frac{T_{\text{fluid,in}} – T_{\text{air,out}}}{T_{\text{fluid,out}} – T_{\text{air,in}}}\right)}$$

The Deadly Phenomenon of Air Stratification

On rooftop make-up air units, outside air enters through an outdoor louver hood, passing through weather filters into the intake chamber.

Because cold Arctic air is extraordinarily dense ($0.088 \text{ lb/ft}^3$ at -15°F vs $0.075 \text{ lb/ft}^3$ at standard temperature), it does not mix smoothly with return air.

Instead, it forms a heavy, razor-thin stratified cold air layer along the bottom twelve inches of the coil face.

While the top rows of the coil may experience warm 60°F air and flowing 150°F fluid, the bottom tube passes are submerged in a sub-zero Arctic freeze stream.

If the unit lacks an engineered **air blender / static mixing baffle**, the localized temperature in that lower quadrant drops below 20°F.

The fluid in the bottom tubes freezes instantly, forming ice dams that block circulation, while the rest of the coil continues to operate normally.

Laminar Boundary Layer Freezing & Reynolds Number Collapse

As heat transfer fluid cools along the tube wall, its kinematic viscosity ($\nu$) increases exponentially.

Consider 50/50 propylene glycol: at 160°F, its kinematic viscosity is only 1.4 centistokes ($cSt$).

As temperature drops to 35°F near the cold tube boundary, viscosity surges to over **12.0 centistokes**.

This sudden viscosity spike collapses the local Reynolds number ($Re = \frac{v \cdot D}{\nu}$) from turbulent flow ($Re > 4,000$) down into sluggish laminar flow ($Re < 2,100$).

In laminar flow, fluid moves in smooth parallel streamlines with near-zero radial mixing.

A stagnant, supercooled boundary layer clings to the inner copper wall.

Even while bulk fluid in the center of the tube continues to circulate at 45°F, the outer boundary layer freezes solid, initiating a catastrophic ice ring that closes off the entire tube bore.

High precision digital hydrostatic pressure gauge testing commercial hydronic loop pressure drop in Broomfield
Figure 2: Master commercial technician performing digital hydrostatic differential pressure testing across a commercial rooftop hydronic coil assembly in Broomfield.

3. Freeze Stat Mechanics: Capillary Tube Physics & Why Safety Controls Fail

If commercial make-up air units have freeze stats installed to prevent freezing, why do coils still burst?

A **Freeze Stat** (low-temperature limit thermostat) is a safety switch designed to trip before ice can form.

It features a vapor-filled or liquid-filled copper capillary sensing tube, typically **twenty feet (20 ft) in length**, woven serpentine-style across the downstream face of the hydronic heating coil.

The internal bellows switch trips whenever any continuous twelve-inch segment of that 20-foot capillary drops below the calibrated setpoint—typically **38°F (3.3°C)**.

How the Safety Interlock Operates

When the freeze stat detects 38°F:

  1. The switch contacts snap open.
  2. The control circuit immediately de-energizes the supply fan motor.
  3. Spring-return motorized actuators snap the outside air dampers tightly shut.
  4. The hydronic control valve is forced 100% wide open to circulate maximum hot boiler water through the coil.

Why Freeze Stats Fail in Real-World Commercial Operation

In our commercial troubleshooting across Broomfield facilities, freeze stats fail due to four specific mechanical errors:

  • Capillary Charge Loss: Over years of rooftop vibration from belt-driven centrifugal blower fans, the capillary copper tube rubs against sharp aluminum fins. A microscopic pinhole develops, releasing the internal vapor charge. The switch either sticks in permanent trip or fails to sense cold temperatures entirely.
  • Improper Weave Geometry: Inexperienced installers coil the 20-foot capillary in a loose bundle near the center of the coil instead of weaving it corner-to-corner across every quadrant. Stratified sub-zero air drafts through unmonitored lower corners, freezing tubes without touching the sensor.
  • Maintenance Bypass Jumpers: In freezing weather, overly sensitive freeze stats may trip repeatedly on start-up. Unqualified building handymen frequently install a temporary electrical jumper wire across the freeze stat terminals to keep the building warm, removing all freeze protection. When night falls and boilers cycle, the coil bursts.
  • Sluggish Damper Actuator Timing: Standard heavy-duty outdoor damper actuators take **45 to 90 seconds** to fully drive closed. When sub-zero winds blast the open louver at 30 MPH, forty-five seconds of unconditioned -15°F air is more than enough time to freeze static copper tubes solid.

4. Ice Expansion Mechanics: 50,000 PSI Hoop Stress & Copper Rupture Failure

What happens inside a copper pipe when water turns to ice?

Water is one of the few anomalous substances that expands when transitioning from liquid to solid.

Upon freezing at 32°F (0°C), liquid water undergoes a **9.0% volumetric expansion**:

$$\frac{\Delta V}{V_0} \approx +0.0905$$

Inside a closed, rigid copper tube with closed balancing valves on both ends, expanding ice acts as an immovable hydraulic piston.

Because ice is practically incompressible, the phase change generates internal hydrostatic pressures exceeding **40,000 to 50,000 PSI**.

Hoop Stress Calculation in ASTM B88 Copper

The circumferential stress exerted on the copper tube wall is modeled by **Barlow’s Hoop Stress Equation**:

$$\sigma_{\text{hoop}} = \frac{P \cdot D_o}{2 \cdot t}$$

Where:

  • $P$ = Internal pressure generated by ice expansion (PSI)
  • $D_o$ = Outer diameter of the tube (e.g., 0.625 inches for 5/8″ commercial coil tube)
  • $t$ = Wall thickness of the copper tubing (typically 0.025 to 0.035 inches for HVAC coils)

For a 5/8″ copper tube with 0.025″ wall thickness under 40,000 PSI ice pressure:

$$\sigma_{\text{hoop}} = \frac{40,000 \cdot 0.625}{2 \cdot 0.025} = \frac{25,000}{0.050} = 500,000 \text{ PSI}$$

The ultimate tensile strength (UTS) of annealed commercial copper is only **30,000 to 40,000 PSI**.

The hoop stress exceeds the ultimate tensile strength of the copper by more than **ten times**.

The copper tube wall bulges, necks down, and rips wide open along its longitudinal seam.

The pipe does not burst at the moment of freezing.

The solid ice plug seals the rupture.

The catastrophic flood occurs hours later, when the kitchen heating fires up and the ice thaws, unleashing 150 GPM of pressurized boiler water through thirty torn copper passes.

Commercial radiant hydronic distribution manifold showing isolating ball valves and balancing flow meters in Broomfield
Figure 3: Commercial hydronic boiler distribution manifold with isolation valves and emergency loop drain assemblies in Broomfield.

5. Glycol Dilution Hazards: Refractometer Testing & Burst vs. Freeze Points

Why do hydronic coils burst even when building owners believe they have glycol in the loop?

Because facilities confuse the **Freeze Point** with the **Burst Protection Point**.

When inhibited propylene glycol mixes with water, it lowers both the freezing crystallization temperature and the volumetric expansion curve:

  • Freeze Point (Slush Point): The temperature at which the first microscopic ice crystals begin to form in the fluid. Fluid remains pumpable slush.
  • Burst Point (Rupture Point): The temperature at which the fluid freezes solid enough to undergo volumetric expansion and rupture copper piping.
Glycol Concentration (% by Volume) Freeze Crystallization Point (°F) Burst Protection Point (°F) Safety Assessment for Colorado Front Range
0% (Plain Municipal Water) +32°F +32°F Extreme Risk: Immediate explosive rupture during freeze event.
20% Propylene Glycol +18°F -10°F Unsafe: Polar vortex temps (-20°F) exceed burst protection limit.
35% Propylene Glycol +2°F -35°F Borderline: Minimum standard for mild interior applications.
50% Propylene Glycol -28°F -60°F Optimal Standard: Complete burst immunity down to -60°F.

In commercial facilities, automatic makeup water feed valves slowly introduce plain tap water whenever minor valve packing or air vent drips occur.

Over two seasons, a 50% glycol loop dilutes down to 22%.

The property manager assumes the system is protected, but when a -18°F cold front hits Broomfield, the fluid freezes solid, ripping copper coil tubes apart.

Our master plumbers test hydronic fluid on site using **Optical Digital Refractometers** calibrated down to 0.1% volume concentration.

We never use cheap floating hydrometer balls, which misread viscosity changes in warm hydronic fluids.

Thermal-Oxidative Glycol Breakdown Chemistry

When diluted glycol cycles continuously through high-temperature commercial boilers, unbuffered glycol degrades into corrosive organic carboxylic acids:

$$\text{C}_3\text{H}_8\text{O}_2 \text{ (Glycol)} + \text{O}_2 \rightarrow \text{C}_3\text{H}_6\text{O}_3 \text{ (Lactic Acid)} \rightarrow \text{C}_2\text{H}_4\text{O}_3 \text{ (Glycolic Acid)}$$

As fluid pH drops below 7.0, acidic glycol aggressively strips protective cuprous oxide films off copper coil tubes, accelerating pinhole wall thinning.

When an Arctic freeze wave hits, the thinned copper walls rupture at significantly lower expansion thresholds.

Fully equipped emergency plumbing diagnostic mobile service van in Broomfield Colorado
Figure 4: Commercial emergency mobile service unit deploying high-output oxy-acetylene silver brazing equipment and ASME repair rigs in Broomfield.

6. Emergency Repair Protocols: ASME Section IX Silver Brazing & Face-Bypass Retrofits

When an MUA coil bursts on a freezing morning, can it be repaired, or must the entire twenty-thousand-dollar unit be replaced?

Ordering a custom commercial hydronic coil from an HVAC manufacturer takes **four to eight weeks of factory lead time**.

A busy commercial kitchen or hotel cannot remain closed for two months without catastrophic business loss.

Our master plumbers execute an emergency **Same-Day ASME Section IX Surgical Brazing Restoration**:

1. Surgical Tube Isolation & Fin Combing

  1. We isolate the MUA hydronic loop and pump out remaining fluid using our portable vacuum recovery system.
  2. We pressurize the isolated coil with 30 PSI dry nitrogen to locate every split tube pass and fractured U-bend.
  3. We carefully comb back crushed aluminum fins using stainless steel fin combs to expose the ruptured copper tubing without tearing adjacent passes.

2. ASME Section IX Oxy-Acetylene Silver Brazing

  1. Standard 50/50 soft solder or 95/5 lead-free solder cannot withstand commercial hydronic thermal cycling and vibration.
  2. We use an oxy-acetylene torch with **AWS BCuP-5 (15% Silver Phos-Copper Alloy)** or **AWS BAg-7 (56% High-Silver Alloy)** engineered for high-vibration commercial HVAC environments.
  3. For longitudinal splits, we either swage an engineered copper sleeve over the rupture or install copper bypass return bends, sealing the alloy at **1,250°F to 1,350°F**.
  4. Continuous nitrogen purging inside the tube prevents internal copper oxide flaking from contaminating boiler valves.

3. 150 PSI Hydrostatic Proof Testing

  1. Following brazing, we pressurize the repaired coil to **150 PSI with clean water for two hours**, monitoring calibrated digital gauges for zero pressure decay.
  2. We re-charge the hydronic loop with virgin 50/50 inhibited propylene glycol, bleed all micro-air bubbles, and restore the kitchen make-up air unit to 100% heating capacity the same day.

Face-and-Bypass Dampers: The Ultimate Mechanical Freeze Protection

Why do progressive commercial facilities in Colorado insist on **Internal Face-and-Bypass Dampers** for rooftop make-up air units?

Standard MUA designs modulate the hot water control valve. When the space approaches the setpoint, the valve throttles down to 10% flow.

This reduction in water velocity is fatal in sub-zero weather.

A face-and-bypass system operates on a radically different thermodynamic principle:

  • Constant 100% Water Velocity: The hydronic coil receives maximum design fluid flow and maximum pump velocity at all times. Fluid never stagnates inside the tubes.
  • Airflow Modulation: Opposed-blade mechanical dampers modulate the airflow. When less heat is needed, the dampers route incoming Arctic air through an internal bypass channel around the coil, blending it downstream in a mixing box.
  • Elimination of Freeze Risk: Because the copper tubes are continuously scoured by high-velocity 150°F fluid, ice can never form on internal tube walls, even when incoming air hits -25°F.

Braze Metallurgy: AWS Type FB3-A Flux & Sil-Fos Alloy Dynamics

When executing field brazing on aged commercial copper coils, copper oxide contamination prevents standard capillary wetting.

Our master plumbers apply high-temperature fluoride-borate paste fluxes conforming to **AWS Type FB3-A**.

The active fluorides dissolve tough cupric oxides, allowing 15% silver alloy to draw deeply into the capillary clearance (0.002 to 0.005 inches) via surface tension.

This produces a monolithic metallurgic joint with tensile shear strengths exceeding 45,000 PSI, outlasting the original copper tube.

7. Real-World Case Studies from Broomfield Commercial Facilities

Examining real-world commercial freeze emergencies reveals how rapid engineering rescues businesses from disaster:

Case Study 1: The Flagship Restaurant Rooftop Rupture on Flatiron Promenade

The Building: A high-volume 350-seat steakhouse and banquet facility on Flatiron Promenade in Broomfield.

The Crisis: During a record-breaking -22°F Arctic snap, the restaurant’s 8,000 CFM rooftop make-up air unit froze at 4:30 AM. When the prep team turned on the kitchen exhaust at 6:00 AM, boiler water surged through twelve ruptured copper U-bends. Pressurized glycol flooded through the ceiling, saturating commercial bread ovens, refrigeration units, and prep lines. Management faced an immediate Saturday night closure with over $35,000 in lost dinner reservations.

Our Master Plumber Diagnosis: We arrived in 20 minutes with our emergency commercial brazing rig. Diagnosis revealed a failed outdoor damper actuator that had stuck 40% open overnight while the circulation pump was off on night setback. Sub-zero air had frozen twelve outer U-bends solid.

The Restoration: Our technicians isolated the rooftop loop, vacuum-extracted water, and swaged twelve copper repair sleeves over the splits. Using oxy-acetylene torches and 15% silver alloy, we brazed all twelve joints under continuous nitrogen purge. We replaced the failed Belimo damper actuator with an ultra-fast spring-return actuator (closing in under 15 seconds) and recharged the loop with fresh 50% inhibited glycol. Pressure testing held flawless at 120 PSI. The restaurant opened on time for dinner service at 4:30 PM.

Case Study 2: Class A Corporate Headquarters Cafeteria in Interlocken

The Building: A corporate campus housing two thousand technology employees with a full commercial cafeteria in Broomfield.

The Crisis: A 12,000 CFM dual-coil MUA suffered a low-temperature freeze stat trip, but a facility technician had installed a jumper across the terminals. Two hours later, three rows of finned copper tubing ruptured, dropping boiler pressure across the entire office tower and flooding server rooms below.

Our Master Plumber Diagnosis: Optical refractometer testing showed the loop glycol had diluted down to only 18% concentration, providing zero protection below +15°F. Severe air stratification had funneled -12°F air directly against the unmonitored lower coil passes.

The Restoration: We isolated the flooded coil, brazed four ruptured tubes, removed the dangerous jumper wire, and re-strung a new 20-foot capillary freeze stat in an engineered serpentine matrix across the entire coil face. We flushed the boiler loop and recharged it with 400 gallons of virgin 50/50 inhibited propylene glycol, providing burst immunity down to -60°F.

Case Study 3: Craft Brewery Kitchen Freeze Split near US-36

The Building: A regional brewery and gastropub operating high-output kitchen fryers and brewing kettles in Broomfield.

The Crisis: A rooftop freeze stat tripped normally during a -15°F cold front, but the hydronic three-way control valve mechanical linkage was stripped, preventing boiler water from bypassing to the coil. The stationary water froze within two minutes, splitting two return headers.

Our Master Plumber Diagnosis: Our emergency hydronic team traced the failure to a stripped Honeywell valve actuator motor.

The Restoration: We brazed the fractured return headers, installed a new commercial Belimo high-torque modulating valve actuator with fail-safe spring return, and re-programmed the building automation freeze protection sequence. Normal brewing and restaurant operations resumed within five hours.

Case Study 4: Commercial Food Processing Plant in North Broomfield

The Building: A 50,000-square-foot industrial bakery and packaging facility operating around the clock.

The Crisis: Sub-zero wind gusts penetrated the intake louvers of a 15,000 CFM makeup air handler. Six copper U-bends burst over the packaging conveyor line, threatening USDA sanitation contamination and halting production.

Our Master Plumber Diagnosis: Intake air stratification had concentrated -18°F air directly against the bottom coil rows, while the freeze stat capillary was mounted on the upper coil quadrant.

The Restoration: We mobilized two master brazing technicians, completed twelve precision silver-brazed swage repairs in under three hours, re-routed the capillary sensor to cover the lower stratified air corridor, and hydrostatically proof-tested the assembly at 140 PSI. Production resumed the same shift, avoiding hundreds of thousands of dollars in spoiled product.

8. Seasonal Freeze Prevention Checklist for Commercial Make-Up Air Systems

Protect commercial kitchen ventilation and heating assets from winter freezing with this annual autumn protocol:

Frequency System Component Maintenance / Inspection Action Engineering Standard / Target Value
Annually (October) Hydronic Fluid Concentration Test fluid with digital optical refractometer Minimum 45% to 50% propylene glycol (Burst protection < -50°F).
Annually (October) Freeze Stat Capillary Calibration Test trip point with aerosol freeze spray; verify 38°F trip Fan shuts off, dampers close, and hydronic valve drives 100% open.
Annually (Pre-Winter) Outdoor Air Damper Actuator Inspect spring-return time on power loss Full stroke closure in under 15 seconds; zero louver seal air leakage.
Monthly (Winter Season) Intake Air Filters Inspect and replace dirty pleated intake air filters Prevent air restriction and uneven air velocity across coil face.
Monthly (Winter Season) Makeup Water Meter Verify automated makeup water feeder meter reads zero Any makeup water consumption indicates loop dilution and active leaks.
Biannually Circulation Pump Amperage Verify circulating pump runs continuously whenever outdoor temp < 35°F Prevent fluid stagnation inside copper tubes during burner cycle-off.

9. Emergency Action Steps: What to Do When an MUA Heating Coil Bursts Right Now

If water is pouring through your ceiling or an MUA coil rupture alarm trips:

  1. Shut Off the Hydronic Isolation Valves Immediately: Locate the mechanical room or rooftop supply and return isolation ball valves for that specific MUA loop and turn them 90 degrees to the closed position. This immediately isolates the leak from the main boiler plant.
  2. Kill Power to the Make-Up Air Unit: Shut off the rooftop electrical disconnect switch to halt supply blower fans and stop sub-zero air ingestion.
  3. Shut Down Electrical Breakers Below: If water is cascading into a commercial kitchen or server room, kill electrical breakers to commercial fryers, stoves, and ceiling light circuits to prevent catastrophic electrical flash-overs.
  4. Do NOT Allow Unqualified Staff to Solder with Soft Lead: Standard hardware store plumbing solder will fail under commercial hydronic pressures. Repairs must be executed using high-temperature 15% silver alloy brazing under nitrogen purge.
  5. Call Licensed Commercial Master Plumbers Immediately: Contact our rapid-response commercial hydronics dispatch at (303) 647-3363. We deploy oxy-acetylene silver brazing rigs, digital refractometers, virgin glycol pumping carts, and certified commercial technicians 24/7 across Broomfield and the Greater Denver Metro area.

Frequently Asked Questions (FAQ)

Why did my Make-Up Air Unit coil freeze if it was running?

Coils freeze while running due to air stratification or valve throttling. Incoming Arctic air (often -15°F) does not mix evenly and forms a dense sub-zero layer along the bottom of the coil. If the modulating water valve throttles down because the kitchen is warm, water velocity slows, and the bottom tubes freeze solid in under 60 seconds.

What temperature should a freeze stat be set at?

Commercial HVAC freeze stats should be set between 38°F and 40°F (3.3°C to 4.4°C). Setting the freeze stat lower risks localized freezing due to temperature differentials across the coil face, while setting it too high causes nuisance tripping during mild cold starts.

Can a burst hydronic commercial coil be repaired without replacing the whole unit?

Yes. In over 85% of cases, our master plumbers repair burst coils on site the same day using ASME Section IX oxy-acetylene silver brazing (using 15% silver alloy). This eliminates the 4 to 8 week factory lead time for custom replacement coils and saves tens of thousands of dollars in facility closure losses.

What glycol concentration is required for commercial coils in Colorado?

In the Colorado Front Range, commercial make-up air units require a minimum of 45% to 50% inhibited propylene glycol by volume. A 50% mix provides freeze protection down to -28°F and burst protection down to -60°F, protecting copper tubes even during sub-zero Arctic vortex events.

Why shouldn’t I jump out a freeze stat that keeps tripping?

Jumping out a freeze stat removes the primary safety device protecting your building. If the coil freezes with the safety bypassed, the tubes will burst under 50,000 PSI ice pressure, causing catastrophic flooding that destroys kitchen equipment, ceilings, and electrical panels.