You walk into the mechanical room of your commercial office building, strip mall, or medical clinic in Broomfield, and your ears are greeted by a deafening, rhythmic hiss. Water is violently surging out of a brass funnel, spilling three gallons a minute across the concrete floor toward the drain. The relief valve on your massive Reduced Pressure Zone (RPZ) backflow preventer has dumped wide open. The floor drain can’t handle the sheer volume. Water is creeping toward the elevator shaft and the main electrical switchgear.
Your maintenance tech reaches out to shut the main isolation valve. But if he turns that handle, the entire building loses domestic water pressure, fire suppression monitoring drops an alarm, and your commercial tenants are forced to evacuate.
What caused your RPZ assembly to dump? Is it catastrophic backflow contamination? A torn elastomeric diaphragm? A speck of pipeline scale wedged in the first check valve? Or did a sudden municipal water main fluctuation trigger a hydraulic zone imbalance?
In Colorado, backflow prevention isn’t merely an administrative checkbox. Under the Colorado Department of Public Health and Environment (CDPHE) Water Quality Control Division Regulation 11, commercial water customers are legally mandated to maintain, test annually, and certify every containment backflow assembly. A malfunctioning RPZ puts the entire municipal potable water grid at risk of lethal contamination.
Let’s dismantle the fluid mechanics inside a Reduced Pressure Zone assembly (ASSE 1013), explore why relief valves violently discharge, walk through field testing protocols using five-valve differential pressure test kits, and outline step-by-step emergency rebuild procedures.

1. The Hydraulics of Cross-Connections: Backsiphonage vs. Backpressure
A cross-connection is any physical link between a potable drinking water supply and a non-potable source of biological, chemical, or radiological pollution. Potable water systems are designed to operate under positive pressure, pushing water in a single direction—from the municipal water treatment plant directly to your faucet.
However, fluid systems obey the laws of physics, not municipal design intentions. Hydraulically, flow always travels from a zone of higher pressure to a zone of lower pressure. When that balance reverses, reverse flow occurs via two distinct hydraulic mechanisms:
A. Backsiphonage (Negative Supply Pressure)
Backsiphonage occurs when pressure in the municipal distribution main drops below atmospheric pressure (14.7 PSI at sea level; roughly 12.1 PSI in Broomfield at 5,420 feet elevation), creating a partial vacuum.
Common Triggers Along the Front Range:
- A high-volume municipal water main break down the street.
- Firefighters hooking ladder trucks to nearby fire hydrants and pulling thousands of gallons per minute to extinguish a structure fire.
- Rapid line draining for scheduled municipal repairs without isolation.
Under backsiphonage, water is literally sucked backward into the drinking supply. If a chemical mixing tank, commercial boiler, or landscape irrigation system is connected without backflow prevention, toxic contaminants are pulled directly into the potable supply.
B. Backpressure (Elevated Downstream Pressure)
Backpressure occurs when the pressure downstream of the water meter exceeds the supply pressure arriving from the city main.
Common Triggers in Commercial Facilities:
- High-pressure commercial boilers generating excessive steam or thermal expansion ($P_{\text{system}} > 100\text{ PSI}$).
- Booster pumps in high-rise commercial buildings over-pressurizing domestic risers.
- Interconnected secondary non-potable water systems (such as agricultural reuse lines or cooling tower loops).
Governed by the Bernoulli principle:
$$P_1 + \frac{1}{2} \rho v_1^2 + \rho g z_1 = P_2 + \frac{1}{2} \rho v_2^2 + \rho g z_2$$
When downstream pressure $P_2$ spikes above supply pressure $P_1$, fluid reverses course at rapid velocity unless physically halted by mechanical check assemblies.
2. How a Reduced Pressure Zone (RPZ) Assembly Works (ASSE 1013)
The Reduced Pressure Principle Backflow Preventer is the absolute gold standard for high-hazard cross-connection containment. It protects against both backsiphonage and backpressure under lethal hazard conditions (such as cyanide electroplating baths, mortuary prep rooms, and chemical fire suppression systems).
An ASSE 1013 RPZ assembly consists of five primary components:
- First Check Valve ($CK_1$): A heavy-duty, spring-loaded check valve designed to hold a minimum pressure drop of 5.0 PSI across its disc under static conditions.
- Differential Pressure Relief Valve ($RV$): An hydraulically balanced discharge valve located between the two check valves. It is mechanically biased by a heavy internal spring that constantly attempts to push the relief valve OPEN to atmosphere.
- Reduced Pressure Zone (The “Zone”): The intermediate hydraulic chamber between Check 1 and Check 2.
- Second Check Valve ($CK_2$): A spring-loaded check valve designed to hold a minimum of 1.0 PSI in the direction of flow to protect against downstream backpressure.
- Four Ball Test Cocks: Precision testing ports installed at strategic locations to allow differential pressure gauge hookups.
| Operational Condition | Supply Pressure ($P_1$) | Zone Pressure ($P_z$) | Differential ($\Delta P = P_1 – P_z$) | Relief Valve State |
|---|---|---|---|---|
| Normal Flow | 80 PSI | 72 PSI | 8.0 PSI | Closed tight ($8.0 > 2.0\text{ PSI}$) |
| Static (No Flow) | 80 PSI | 74 PSI | 6.0 PSI | Closed tight ($6.0 > 2.0\text{ PSI}$) |
| Fouled Check 1 | 80 PSI | 78.5 PSI | 1.5 PSI | DISCHARGING WIDE OPEN ($1.5 < 2.0\text{ PSI}$) |
| Backsiphonage | 0 PSI (Vacuum) | 0 PSI (Vent to atmosphere) | 0.0 PSI | DUMPING TO ATMOSPHERE |
The Critical Mechanical Equilibrium
The relief valve’s internal diaphragm has supply pressure ($P_1$) acting on one side, pushing it CLOSED. On the other side, zone pressure ($P_z$) PLUS the mechanical relief valve spring are pushing it OPEN.
Under industry manufacturing standards (ASSE 1013 / AWWA C511), the relief valve spring is calibrated to open whenever the differential pressure between the supply and the zone drops below 2.0 PSI:
$$\text{Relief Valve Opens if: } (P_1 – P_z) \le 2.0\text{ PSI}$$
Because the first check valve is engineered to create a minimum 5.0 to 8.0 PSI pressure drop, the zone is always maintained at a significantly lower pressure than the supply line. Even if both checks fail, gravity and atmospheric venting ensure that polluted water drops out the bottom onto the floor rather than crawling backward into the public water supply.
3. Why Is Your RPZ Spitting or Dumping Water? Diagnostic Guide
A dumping relief valve is the most frequent emergency call commercial plumbers receive. Don’t panic. Water pouring from the funnel means the valve is doing its job: sacrificing domestic pressure to protect drinking water.

Here is how our certified backflow technicians diagnose the exact failure mode within five minutes:
Scenario 1: Continuous, Violent High-Volume Discharge
Water roars out of the relief port continuously, whether the facility is using water or sitting idle.
- Root Cause A: Fouled First Check Valve ($CK_1$). A particle of pipe scale, copper shaving, or gravel from a municipal main repair has lodged between the rubber disc and the stainless-steel seat. Water leaks past $CK_1$, pressurizing the intermediate zone. As $P_z$ climbs, the differential drops below 2.0 PSI. The relief valve snaps wide open.
- Root Cause B: Ruptured Relief Valve Diaphragm. The flexible EPDM sensing diaphragm inside the relief valve has torn or split. Supply pressure can no longer pressurize the “close” side of the diaphragm chamber. The internal spring pushes the relief valve stem open, dumping continuously.
Scenario 2: Intermittent “Spitting” or “Chattering”
The relief valve spits a cup of water every few minutes, or coughs violently whenever a commercial flushometer or solenoid valve closes down the hall.
- Root Cause: Supply Line Pressure Fluctuations & Water Hammer. When a nearby commercial fixture snaps shut, a shockwave travels backward through the pipe. Supply pressure ($P_1$) momentarily drops while the intermediate zone pressure remains temporarily trapped at a higher level. The brief pressure differential drop causes the relief valve to burp.
- Solution: Installing an upstream water hammer arrestor or a high-capacity soft-seated check valve upstream dampens the hydraulic pulse and stops the chattering.
Scenario 3: Relief Valve Dumps ONLY During Downstream Usage
The unit stays dry all night when the building is closed. But the moment tenant faucets turn on in the morning, water begins pouring from the relief vent.
- Root Cause: Fouled Second Check Valve ($CK_2$) with Simultaneous Backpressure. Elevated downstream pressure or thermal expansion pushes back through a defective second check, over-pressurizing the intermediate zone while domestic flow is moving.
4. Step-by-Step RPZ Field Testing Protocol (ASSE Certified 5-Valve Kit)
Under Colorado CDPHE Regulation 11, backflow assemblies must be tested by an ASSE 5110-certified backflow tester using an annual NIST-calibrated differential pressure gauge. Here is the strict testing sequence:
🧪 The ASSE Field Test Sequence
- Pre-Test Notification & Visual Inspection: Notify building management. Inspect the installation for required clearances (minimum 12 inches off floor, maximum 60 inches, air gap funnel installed). Verify that the test cocks are cleared of debris by briefly blowing them out with water.
- Test 1: Relief Valve Opening Point. Connect the High-Pressure hose of the test kit to Test Cock 2 (upstream of $CK_1$) and the Low-Pressure hose to Test Cock 3 (the Zone). Close shutoff valve #2. Bleed the gauge valves. Slowly crack open the needle bypass valve to bleed zone pressure. Observe the differential gauge needle. The relief valve must spit or open before the differential drops to 2.0 PSI (standard acceptable range is 2.2 to 3.5 PSI). If it drops below 2.0 PSI or fails to open, the assembly FAILS.
- Test 2: Tightness of Second Check Valve ($CK_2$). With shutoff #2 closed and the differential gauge reading the drop, pressurize the downstream side of $CK_2$ via a high-pressure bypass hose to Test Cock 4. If the zone differential pressure drops, $CK_2$ is leaking and FAILS.
- Test 3: Tightness of First Check Valve ($CK_1$). Observe the static differential across $CK_1$. The differential reading must hold steady at 5.0 PSI or greater. If the differential slowly drops toward zero, $CK_1$ is fouled with debris or its rubber disc is damaged. The assembly FAILS.
5. Emergency Field Rebuild: Step-by-Step Restoration
When an RPZ fails its annual certification or dumps water across a commercial floor, a licensed master plumber doesn’t immediately condemn the \$3,000 brass casting. Ninety percent of assemblies can be completely rebuilt on-site in under ninety minutes using factory-authorized elastomer repair kits.
Step 1: Isolation and Depressurization
Close Shutoff Valve #2 (downstream) first, then close Shutoff Valve #1 (upstream). Crack open Test Cocks 2, 3, and 4 to completely depressurize the body. Water will drain from the relief valve until the internal chambers are empty.
Step 2: Check Valve Disassembly & Inspection
Remove the access cover bolts or top retainer clamps using a socket wrench. Take care: internal check modules are spring-loaded. Remove Check 1 and Check 2 assemblies.
Inspect the stainless-steel seating rings. Look for wire-drawing (microscopic grooves cut into metal by high-velocity water jets) or mineral scale crust. Wipe the seats clean using a lint-free shop towel or a nylon scouring pad. Never use steel wool or metal rasps on brass or stainless seating surfaces.
Step 3: Replacing Elastomer Discs
Unbolt the disc retainers. Peel out the old EPDM rubber discs. Inspect them for foreign object imprints (sand, copper burrs) or chemical degradation (swelling caused by chlorine or chloramines). Flip the disc over if it is dual-sided, or press in brand-new factory silicone/EPDM discs. Torque the retainer screw to manufacturer specifications (typically 25 to 35 in-lbs).
Step 4: Rebuilding the Relief Valve Module
Unbolt the relief valve housing cover. Slowly release spring tension. Pull the relief valve stem, piston, and rolling diaphragm assembly.
Inspect the sensing diaphragm for pinholes by holding it up to a bright LED light. Coat new rubber O-rings with NSF-61 certified food-grade silicone grease (Super Lube or Dow Corning 111). Never use petroleum-based grease, which rots EPDM rubber within weeks. Reassemble the relief valve stem and tighten housing bolts evenly in a star pattern.
Step 5: Slow Re-Pressurization & Recertification
Slowly open Shutoff Valve #1 to bleed air through the top test cocks until solid water streams emerge. Close the test cocks. Allow the intermediate zone to pressurize. The relief valve may give one brief burp, then seal shut with absolute silence.
Re-attach the 5-valve differential test gauge, re-run the three certified test protocols, and record the passing values on the state-mandated CDPHE compliance certificate.
6. Colorado Winter Freeze Mitigation for Commercial Backflows
In the Colorado Front Range, many commercial backflows are installed outdoors on dedicated irrigation mains, car washes, or outdoor hospitality zones. When sub-zero arctic blasts strike, these uninsulated brass assemblies freeze and shatter within hours.

Essential Winterization Standards
- ASAE / ASSE 1060 Enclosures: Outdoor commercial backflows must be housed in an insulated, fiberglass or aluminum “Hot Box” rated to ASSE Standard 1060 (Class 1 heated enclosure capable of maintaining 40°F in -30°F outdoor ambient cold).
- Self-Regulating Heat Trace: Apply commercial-grade, self-regulating 120V heat trace cable (minimum 5 watts per foot) spiraled around the brass casting, wrapped in closed-cell elastomeric foam pipe insulation.
- Seasonal Winter Blow-Outs: Landscape irrigation backflow assemblies must be completely isolated, drained, and blown out with high-volume, low-pressure compressed air (50 to 60 PSI at 80 CFM) before the first hard freeze in October.
Commercial Backflow FAQs
What is the difference between a Double Check (DC) and an RPZ?
A Double Check Valve Assembly (ASSE 1015) contains two spring check valves but has NO hydraulic relief valve. It is only permitted for low-hazard non-toxic cross-connections (such as standard non-chemical fire sprinkler lines). A Reduced Pressure Zone assembly (ASSE 1013) contains two independent check valves separated by an atmospheric differential relief valve. It is legally mandated for high-hazard toxic applications because even if both checks fail mechanically, the intermediate zone dumps contaminated water onto the floor rather than allowing it into the drinking water.
Who is authorized to test backflow preventers in Colorado?
Under CDPHE Regulation 11, only technicians holding an active Cross-Connection Control Tester certification from an accredited agency (such as ASSE 5110 or ABPA) can perform legal certification tests. In addition, testers must have their differential pressure test gauges recalibrated and certified annually against NIST standards. Handymen, standard plumbers without backflow credentials, and building maintenance staff are not legally permitted to sign state compliance documentation.
Can an RPZ backflow preventer be installed vertically?
Only if the specific manufacturer model is explicitly certified and stamped for vertical installation by ASSE and USC Foundation for Cross-Connection Control. Most standard RPZ assemblies (such as Watts 009 or Febco 860) are certified strictly for horizontal orientation with the relief valve pointing straight down. Installing a horizontal-only RPZ in a vertical run causes the internal gravity-assisted relief valve mechanism to bind, voiding code compliance and triggering continuous discharge.
Why can’t I pipe my RPZ relief valve discharge port directly into a sewer drain?
Plumbing codes (IPC Section 608.15.2 and UPC Section 603.4.2) strictly require an approved, indirect waste air gap between the relief valve discharge funnel and the drainage receptacle. The air gap must be at least twice the diameter of the supply pipe (and never less than 1 inch). If you hard-pipe an RPZ relief port directly into a drain without an air gap, a municipal sewer backup would push raw sewage straight backward through the open relief valve into your potable water supply!