At four o’clock on a Monday morning inside a ten-story corporate office tower in Interlocken, a major regional medical pavilion, or an industrial processing plant in Broomfield, Colorado, an emergency water alarm screams. Down in the sub-grade domestic water service entrance vault, a deafening roar of rushing water echoes off concrete walls.
The building’s six-inch commercial Reduced Pressure Zone (RPZ) backflow preventer has opened wide.
Its atmospheric relief valve port is dumping **two hundred and fifty gallons of potable water per minute** directly onto the mechanical room floor.
The vault’s floor drain has surcharged under the hydraulic tsunami.
Water is rising rapidly toward emergency electrical switchgear panels and variable frequency drive pump skids.
Inside the primary mechanical room, building managers face a terrible dilemma:
Shut off the main OS&Y gate valves and cut off all domestic water to hundreds of commercial tenants, or watch the building basement drown under thousands of gallons of municipal water.
A continuously dumping RPZ backflow preventer is not a minor leak.
It is an immediate high-stakes mechanical emergency governed by **ASSE Standard 1013, International Plumbing Code (IPC) Section 608**, state drinking water cross-connection regulations, and severe hydraulic differential pressure mechanics.
When particulate debris fouls an internal check valve seat or an elastomeric sensing diaphragm ruptures, the valve does exactly what it was engineered to do: it dumps water to atmosphere to protect the public water supply from chemical contamination.
Let’s examine the fluid dynamics of reduced pressure backflow prevention, calculate differential pressure gradients across the intermediate relief chamber, diagnose check valve fouling mechanisms, review ASSE 5110 testing procedures, and detail master plumber rebuild protocols across the Colorado Front Range.

1. The Mechanical Engineering of ASSE 1013 RPZ Assemblies & Hydraulic Zone Mechanics
Why do commercial water services mandate Reduced Pressure Zone (RPZ) assemblies instead of simple double check valves?
The answer comes down to **High-Hazard Contamination Protection**.
Under **Colorado Department of Public Health and Environment (CDPHE) Regulation 11 and IPC Section 608.16**, any commercial facility with cross-connections to toxic chemicals, boilers, cooling towers, medical equipment, or commercial kitchens is classified as a high-hazard health risk.
In high-hazard facilities, mechanical check valves alone are not trusted.
Check valves can stick open on mineral scale, rust nodules, or gravel.
An **ASSE Standard 1013 Reduced Pressure Zone (RPZ) Assembly** solves this through hydraulic fail-safe architecture:
- First Check Valve (Check 1): A heavy spring-loaded check valve engineered to create a mandatory hydraulic pressure drop of at least **5.0 to 8.0 PSI** across its seat.
- Intermediate Reduced Pressure Chamber: A fluid zone located between the two check valves that always operates at a lower hydraulic pressure than the incoming municipal supply line.
- Differential Pressure Relief Valve: A hydraulically balanced diaphragm-actuated discharge valve monitoring the pressure difference between supply pressure and the intermediate chamber.
- Second Check Valve (Check 2): A secondary spring-loaded check valve (minimum 1.0 to 2.0 PSI closing bias) isolating building downstream piping from the intermediate chamber.
- Four Calibrated Test Cocks: Precision needle valves enabling certified backflow testers to measure exact differential pressures down to 0.1 PSI.
The Governing Differential Pressure Equation ($\Delta P$)
The operation of the internal relief valve is governed by the differential pressure balance across its flexible sensing diaphragm:
Where:
- $P_{\text{supply}}$ = High-pressure municipal water acting on the top (reference side) of the relief valve diaphragm ($PSI$)
- $P_{\text{intermediate zone}}$ = Reduced pressure fluid acting on the bottom (sensing side) of the relief valve diaphragm ($PSI$)
- $F_{\text{spring}}$ = Mechanical force of the internal relief valve spring calibrated to open the port whenever $\Delta P \le 2.0 \text{ PSI}$
| Operational State | Measured Differential ($\Delta P$) | Diaphragm Hydraulic Balance | Relief Valve Physical Behavior |
|---|---|---|---|
| Normal Static / Flowing | $\Delta P \ge 5.0 \text{ to } 8.0 \text{ PSI}$ | Supply pressure easily overcomes internal spring force. | Closed tight. Zero water discharge from relief port. |
| Check 1 Fouled with Silt | $\Delta P \le 2.0 \text{ PSI}$ (Collapsing) | Intermediate zone pressure rises toward supply pressure. | Relief valve snaps wide open. Dumps water continuously. |
| Backsiphonage (City Main Vacuum) | $\Delta P \le 0 \text{ PSI}$ (Negative Differential) | Intermediate zone pressure exceeds collapsing supply pressure. | Full port dumping. Air enters port, breaking vacuum. |
| Ruptured Sensing Diaphragm | $\Delta P$ cannot equalize across torn rubber | Internal spring pushes valve stem open mechanically. | Continuous catastrophic deluge regardless of line pressure. |
Look closely at the table above.
The relief valve does not need an electrical sensor, computer controller, or motorized actuator.
It is powered entirely by hydraulic physics.
If anything compromises the 5.0+ PSI pressure differential, the internal stainless steel spring pushes the relief valve stem open, discharging water to atmosphere.
The valve physically sacrifices water to guarantee contaminated liquid can never cross into the public main.
Orientation Dynamics: Horizontal vs. Vertical-Up ASSE Approvals
Can a commercial RPZ backflow preventer be mounted vertically to save mechanical room space?
Only if the specific valve body holds an explicit **ASSE 1013 Vertical-Up Certification** from the manufacturer.
Standard horizontal RPZ bodies rely on gravity to assist in centering the internal relief valve diaphragm and check discs.
If an unapproved horizontal valve is installed in a vertical orientation:
- Gravity pulls the heavy bronze check discs sideways against their guide sleeves, creating asymmetric friction wear.
- The relief valve diaphragm hangs off-center, causing the rubber disc to cock and drag against the seat ring.
- The intermediate chamber drainage is impaired, trapping air bubbles that cause false differential pressure collapse and continuous nuisance dumping.
Front Range Chloramine Water Chemistry & Elastomer Degradation
In Broomfield and the surrounding Denver Metro area, municipal water treatment facilities utilize **Chloramines (Monochloramine, $\text{NH}_2\text{Cl}$)** rather than free chlorine for secondary distribution disinfection.
While chloramines reduce trihalomethane formation, they are aggressive toward standard plumbing rubber.
Monochloramine molecules diffuse into sulfur-cured EPDM rubber matrices, attacking the carbon-sulfur chemical cross-links:
This chemical degradation causes the rubber to swell by up to 15% in volume, soften, and develop sticky blisters.
When the rubber disc swells, it extrudes past its metal retaining plate. The swollen rubber binds in the seat bore or tears during closing, triggering sudden check valve failure.
Our master plumbers rebuild commercial backflow assemblies using **Peroxide-Cured EPDM or Fluoroelastomer (Viton)** parts engineered specifically for high-chloramine municipal supplies.
2. Root Causes of Continuous Relief Valve Dumping & Catastrophic Floods
Why does an RPZ backflow preventer suddenly start gushing water like a fire hydrant?
In our master commercial troubleshooting across Broomfield, five distinct mechanical failures trigger continuous discharge:
1. First Check Valve (Check 1) Debris Fouling
This accounts for over 70% of all emergency service calls.
When municipal water utilities repair broken water mains along 120th Avenue or Highway 287, gravel, sand, iron rust flakes, and pipe dope enter the municipal main.
When water service restores, this debris charges into the building service header.
A tiny piece of granite gravel or pipe scale lodges between the Check 1 rubber disc and the bronze seat ring.
Because Check 1 cannot seat bubble-tight, municipal supply water bleeds directly into the intermediate reduced pressure chamber.
The intermediate zone pressure rises until $\Delta P$ collapses below 2.0 PSI.
The relief valve snaps open, dumping hundreds of gallons per minute until technicians isolate the assembly.
2. Second Check Valve (Check 2) Backpressure Fouling
If downstream building pressure rises above supply pressure (caused by boiler thermal expansion, multi-stage booster pump surges, or elevator hydraulic cooler backpressure) and Check 2 is fouled with mineral scale, high-pressure downstream water flows backward into the intermediate zone.
This backpressure equalizes the intermediate chamber with the supply line, dropping $\Delta P$ and triggering continuous relief valve discharge.
3. Relief Valve Sensing Diaphragm Rupture
The flexible fabric-reinforced EPDM diaphragm separating the high-pressure reference chamber from the low-pressure intermediate chamber flexes millions of times over its lifespan.
Chloramine disinfection chemicals in Front Range water accelerate rubber embrittlement.
Under a sudden water hammer pressure spike, the hardened diaphragm tears along its outer bead.
High-pressure reference water shoots through the torn rubber directly into the discharge port, locking the relief valve in permanent full-flow discharge.
4. Supply Line Pressure Fluctuations & Water Hammer “Spitting”
If an RPZ intermittently spits water in short burps rather than dumping continuously, the building is suffering from **Supply Pressure Instability**.
When high-capacity commercial equipment downstream (such as large flushometer banks or rapid-closing solenoid valves on commercial dishwashers) snaps shut, Joukowsky pressure waves bounce off Check 1.
A sudden drop in supply line pressure temporarily lowers $P_{\text{supply}}$ faster than the intermediate chamber can adjust, causing the relief valve to burp water before resealing.
5. Relief Valve Guide Stem Binding & Mineral Scale Seizure
In hard water areas with high dissolved calcium carbonate, mineral scale crusts over the relief valve bronze guide stem.
When the relief valve opens during a routine pressure blip, the scaled stem jams on its guide bushings, preventing the spring from pulling the disc back onto its seat.

3. Hydraulic Discharge Flow Rates & IPC Section 608 Air Gap Drainage Sizing
How much water can a commercial RPZ relief valve actually dump onto a floor?
Most building managers mistakenly assume a standard 3-inch or 4-inch floor drain can handle RPZ discharge.
They are wrong.
Under full differential relief failure, the relief port behaves as an open hydraulic orifice connected to a high-pressure municipal main.
Discharge flow rate through the relief valve orifice is calculated using the **Torricelli Orifice Flow Equation**:
Where:
- $Q$ = Volumetric discharge rate ($ft^3/s$ or $GPM$)
- $C_d$ = Discharge coefficient of the relief port orifice (typically $0.62 \text{ to } 0.70$)
- $A_{\text{orifice}}$ = Cross-sectional area of the relief port
- $\Delta P$ = Operating line pressure ($PSI$)
- $g$ = Gravitational acceleration ($32.2 \text{ ft/s}^2$)
| RPZ Valve Size | Relief Port Orifice Diameter | Peak Discharge at 60 PSI Line Pressure | Peak Discharge at 150 PSI (Front Range Main) | Minimum Drainage Capacity Required |
|---|---|---|---|---|
| 1-1/2 Inch RPZ | 1.25 Inches | 55 GPM | 90 GPM | 3-Inch Gravity Floor Drain |
| 2-Inch RPZ | 1.75 Inches | 110 GPM | 180 GPM | 4-Inch Gravity Floor Drain |
| 4-Inch RPZ | 3.00 Inches | 290 GPM | 480 GPM | 6-Inch Drain or Sump Pit |
| 6-Inch RPZ | 4.50 Inches | 420 GPM | 710 GPM | 8-Inch Gravity Main or Dual Sump |
Look at the numbers in the table above.
A 4-inch commercial RPZ backflow preventer operating on a 150 PSI Front Range water service can dump **480 Gallons Per Minute**.
A standard 4-inch gravity floor drain on a 1/4″ per foot slope can evacuate only **120 GPM**.
If a 4-inch RPZ fails wide open, water will accumulate on the mechanical room floor at a net rate of **360 GPM**.
Within twenty minutes, three feet of standing water will submerge mechanical equipment.
IPC Section 608.15.2 Air Gap Mandates
To prevent dirty flood water from being siphoned back into the drinking water line during relief discharge, **IPC Section 608.15.2** enforces strict physical air gap dimensions:
A solid pipe or garden hose must never be screwed directly into an RPZ relief port.
It must discharge through a factory-engineered, code-approved **Air Gap Funnel fitting** to provide an absolute physical separation between drinking water and drainage piping.

4. ASSE 5110 Certified Diagnostic Testing: Step-by-Step Field Protocol
How does an ASSE 5110 certified backflow technician pinpoint the exact fouled component without ripping the valve apart blindly?
We connect a calibrated **5-Valve Differential Pressure Test Kit** (such as a Mid-West Instrument Model 830 or Apollo 40-200) to the four test cocks and execute the **Standard ASSE 5110 Diagnostic Procedure**:
Test 1: Relief Valve Opening Point Verification
- We install the high-pressure hose on Test Cock 2 (upstream of Check 1) and the low-pressure hose on Test Cock 3 (intermediate zone).
- We bleed air from all test hoses and slowly open the needle bypass valve to bleed water from the high side to the low side, simulating a failing Check 1.
- We observe the differential pressure gauge needle as differential pressure drops.
- The relief valve must open and discharge water before differential pressure drops below **2.0 PSI**. If the needle reads 1.4 PSI or 0.8 PSI before discharge begins, the relief valve spring has weakened or the stem is binding, failing the certification test.
Test 2: Check Valve 2 Tightness Against Backpressure
- We maintain the high hose on Test Cock 2 and low hose on Test Cock 3.
- We introduce high-pressure water from Test Cock 2 into Test Cock 4 (downstream of Check 2) through an external bleed hose.
- We observe Test Cock 3 and the relief valve port. If intermediate zone pressure rises or water dumps from the relief port, Check Valve 2 is leaking backward, allowing downstream contaminated water into the intermediate chamber.
Test 3: Check Valve 1 Static Closing Bias
- We close the downstream shutoff valve (Shutoff 2).
- We observe the static differential pressure gauge. The gauge must hold steady at a minimum differential of **5.0 PSI** (typically 6.5 to 8.5 PSI).
- If the differential gauge needle slowly drops down toward 2.0 PSI and the relief valve begins to weep, Check Valve 1 is fouled with debris and cannot hold its seat.

5. Surgical On-Site Rebuild: Check Valve Lapping, Diaphragms & Flood Protection Valves
Once the failure is diagnosed, how do our master plumbers restore building water service within hours?
We execute a **Surgical Clean-and-Rebuild Protocol**:
1. High-Velocity Line Purging
- Before opening the valve body, we isolate Shutoff 2 and open Test Cock 1 wide open under full 150 PSI line pressure.
- This flushes loose granite sand and pipe rust out of the municipal line, preventing fresh debris from fouling the newly rebuilt check valves.
2. Module Extraction & Stainless Steel Seat Lapping
- We remove the heavy cast-iron or stainless steel access covers.
- We extract Check Module 1, Check Module 2, and the relief valve sub-assembly.
- We inspect the bronze or stainless steel seat rings. If debris has scored the seat edge, we lap the seat ring with a precision diamond lapping stone to restore a pristine mirror finish.
- We install brand new OEM silicone or Viton check discs, replacing all guide O-rings and stainless steel return springs.
3. Relief Valve Diaphragm Assembly Replacement
- We replace the flexible fabric-reinforced EPDM sensing diaphragm, rolling diaphragm seals, and stainless relief spring.
- We coat all dynamic seals with food-grade NSF-61 approved silicone lubricant.
- We torque body cover bolts to factory specifications using a calibrated mechanical torque wrench.
4. Emergency Electronic Flood Protection Retrofits
To prevent future vault inundations from destroying commercial mechanical rooms, we install automated **Flood Protection Shutoff Modules** (such as Watts FloodSafe or Apollo SmartPRV):
- An electronic sensor grid is mounted inside the air gap funnel.
- If the relief valve dumps continuously for more than **fifteen seconds**, the controller immediately triggers a fast-acting motorized butterfly or ball valve on the main supply line.
- The supply is shut down automatically, limiting total discharge to less than fifty gallons and broadcasting an immediate alert to the building automation system.
6. Real-World Case Studies from Broomfield Commercial Facilities
Reviewing real-world commercial backflow emergencies reveals how rapid master plumbing engineering prevents catastrophic operational downtime:
Case Study 1: The Ten-Story Corporate Office Vault Flooding in Interlocken
The Building: A premier Class A corporate headquarters in Interlocken Business Park, Broomfield.
The Crisis: At 3:45 AM, the main 6-inch Watts 909 RPZ backflow preventer failed wide open in the basement sub-grade vault. Pressurized water at 165 PSI was spewing from the 4-inch relief port at 400 GPM. The vault floor drain surcharged immediately. By the time security arrived, two feet of standing water had reached the transformer footing. Facility directors faced shutting down power and evacuating twelve hundred corporate workers.
Our Master Plumber Diagnosis: We arrived in 16 minutes with our commercial backflow emergency unit. We isolated the main OS&Y valves and pumped out the vault using high-capacity submersible trash pumps. ASSE 5110 diagnostic testing revealed that Check 1 was completely jammed open by a 3/4-inch piece of asphalt aggregate introduced during municipal roadwork on 96th Street.
The Restoration: We disassembled Check Module 1, extracted the aggregate stone, and inspected the stainless seat ring. The stone had dented the rubber disc, but the seat was intact. We installed a fresh factory elastomer rebuild kit, re-seated Check 1, and overhauled the relief valve diaphragm. We certified the valve with our calibrated differential test kit, logging a healthy 7.4 PSI differential. Total downtime was 2.5 hours. Corporate operations began without disruption.
Case Study 2: Craft Brewery Processing Floor Deluge near Highway 287
The Building: A regional craft brewing and canning facility operating high-capacity steam boilers and fermentation tanks in Broomfield.
The Crisis: The brewing facility’s 3-inch Wilkins 975XL RPZ backflow preventer began discharging continuously onto the canning floor during a live packaging run. The plant operator could not shut off water without spoiling twenty thousand gallons of craft beer in the mash tuns.
Our Master Plumber Diagnosis: We connected our 5-valve test kit under active production flow. Test 2 revealed that high-pressure steam backpressure from an un-trapped boiler feedwater economizer had blown back through Check 2, elevating intermediate zone pressure and forcing the relief valve open. Check 2’s rubber disc had hardened and cracked from exposure to 190°F steam condensate.
The Restoration: We engaged an emergency temporary bypass loop with an inline backflow assembly, allowing brewing production to proceed without pause. We replaced Check 2’s compromised rubber with a high-temperature Viton commercial disc rated for 210°F, installed a downstream temperature relief valve, and re-tested the assembly to full ASSE 1013 standards. Zero product was lost.
Case Study 3: Medical Surgical Pavilion Vault Deluge on Summit Blvd
The Building: A multi-tenant surgical hospital housing ambulatory surgery suites and cardiac imaging labs in Broomfield.
The Crisis: A 4-inch RPZ backflow valve relief port dumped water continuously into an exterior concrete pit. The pit sump pump failed, sending groundwater and chlorinated domestic water over the building footer and into the basement medical imaging suite.
Our Master Plumber Diagnosis: Diagnostic differential testing revealed that the relief valve’s fabric-reinforced EPDM diaphragm had suffered a 2-inch tear along its outer clamp ring, mechanically locking the valve stem open.
The Restoration: We replaced the ruptured diaphragm assembly with a heavy-duty chloramine-resistant fluorocarbon diaphragm, installed an automated electronic flood sensor with motorized shutoff interlocks, and recertified the valve with state health department documentation in under three hours.
Case Study 4: Senior Living Community Thermal Expansion Lockout on 120th Avenue
The Building: A 150-unit senior living campus with a centralized commercial boiler room on 120th Avenue in Broomfield.
The Crisis: Every afternoon at 2:00 PM, the building’s 3-inch RPZ backflow preventer began discharging heavily into the boiler room floor drain, discharging over 800 gallons over three hours. Maintenance had replaced the relief valve assembly twice, but the dumping persisted daily at the exact same hour.
Our Master Plumber Diagnosis: We installed continuous electronic pressure data loggers on all four test cocks. At 1:30 PM, the campus commercial kitchen completed lunch dishwashing, and all domestic hot water taps closed. Four 100-gallon commercial hot water storage tanks heated up from 110°F to 140°F. Because the closed plumbing loop lacked an operable thermal expansion tank (the existing expansion tank bladder was waterlogged), thermal expansion spiked downstream building pressure from 65 PSI to 145 PSI. This massive backpressure forced water backward across a slightly scaled Check 2, equalizing the intermediate chamber and forcing the relief valve open.
The Restoration: We replaced the waterlogged 50-gallon thermal expansion tank with an ASME Section VIII rated bladder expansion tank pre-charged to 65 PSI. We cleaned and lapped Check 2’s seat ring. When water heaters fired, thermal expansion was absorbed cleanly by the new bladder, keeping downstream pressure below 70 PSI. Relief valve dumping ceased completely.
7. Preventive Maintenance Checklist for Commercial RPZ Backflow Assemblies
Guarantee reliable operation and maintain mandatory CDPHE drinking water compliance with this annual protocol:
| Frequency | System Component | Inspection & Testing Action | Compliance Standard / Benchmark |
|---|---|---|---|
| Monthly | Relief Valve Discharge Port | Visual inspection of air gap funnel for continuous weeping or spitting | Zero continuous discharge; port completely dry during steady flow. |
| Monthly | Mechanical Vault Floor Drain | Inspect drain grate for lint, dirt, and standing water accumulation | Unobstructed gravity flow; clear path to floor drain or sump basin. |
| Quarterly | Test Cock Needle Valves | Operate and flush test cocks 1 through 4 to clear sediment build-up | Clean water stream; zero packing gland leakage when closed. |
| Annually (Mandatory) | Complete ASSE 5110 Recertification | Full 3-test differential pressure certification by ASSE certified tester | Relief opening $\ge 2.0 \text{ PSI}$; Check 1 drop $\ge 5.0 \text{ PSI}$; Check 2 tight. |
| Every 3 to 5 Years | Full Elastomer Rebuild | Teardown inspection: replace check discs, diaphragms, and O-rings | Use only OEM certified parts; lap bronze seat rings to mirror finish. |
| Every 3 to 5 Years | Internal Stainless Springs | Inspect Check 1, Check 2, and relief springs for corrosion or fatigue | Replace springs to maintain precise design closing force. |
8. Emergency Action Steps: What to Do When Your RPZ Backflow Dumps Water Right Now
If your commercial RPZ backflow preventer relief valve is dumping water onto the floor:
- Locate the Shutoff Valves on the RPZ: An RPZ assembly has two shutoff valves: Shutoff 1 (upstream on the inlet) and Shutoff 2 (downstream on the outlet).
- Close Shutoff Valve 2 (Downstream) First: Turn Shutoff 2 clockwise to close it. If the relief valve stops dumping water immediately, the problem is downstream backpressure (Check 2 failure). If water continues to dump, the problem is upstream debris in Check 1 or a torn relief diaphragm.
- Do NOT Cap or Plug the Relief Port: Never install a pipe plug, cap, or clamp onto the relief valve discharge port. Capping the relief port destroys the backflow protection, builds internal hydraulic lock, and forces contaminated chemical water backward into drinking water taps.
- Clear the Vault Floor Drain: Remove any trash, boxes, or debris blocking the mechanical room floor drain to allow water to evacuate while technicians mobilize.
- Call ASSE-Certified Master Plumbers Immediately: Contact our rapid-response commercial backflow emergency team at (303) 647-3363. We deploy calibrated 5-valve differential test kits, factory OEM rebuild modules (Watts, Ames, Wilkins, Apollo), high-capacity submersible extractors, and ASSE 5110 certified master plumbers 24/7 across Broomfield and the Greater Denver Metro area.
Frequently Asked Questions (FAQ)
Why is my commercial RPZ backflow preventer dumping water continuously?
An RPZ dumps water when the hydraulic pressure differential between the incoming supply line and the intermediate chamber drops below 2.0 PSI. This is most commonly caused by pipe scale or gravel jamming open the first check valve, high downstream backpressure leaking past the second check valve, or a ruptured flexible sensing diaphragm.
What is the difference between an RPZ spitting water and dumping water?
Spitting water (intermittent short burps) is typically caused by sudden supply line pressure fluctuations or water hammer shock waves from downstream fast-closing valves. Continuous dumping (a steady high-volume cascade) indicates a mechanical failure, such as a fouled check valve seat or a torn relief valve diaphragm.
Can I install a pipe plug or cap on the relief valve to stop the flood?
No. Plugging or capping an RPZ relief port is strictly illegal under the International Plumbing Code and state drinking water regulations. Capping the relief port removes the fail-safe cross-connection protection, allowing contaminated industrial wastewater to siphon directly into drinking water pipes during a pressure drop.
How much water can a commercial 4-inch RPZ backflow discharge?
Under full relief failure at 150 PSI line pressure, a 4-inch commercial RPZ backflow preventer can discharge up to 480 Gallons Per Minute. Because standard gravity floor drains handle only 100 to 150 GPM, an unmonitored failure can flood a mechanical vault with multiple feet of standing water in under thirty minutes.
How often does an RPZ backflow preventer need to be tested in Colorado?
Under Colorado Department of Public Health and Environment (CDPHE) Regulation 11 and local municipal codes, all commercial RPZ backflow preventers must be tested and certified upon installation, after any repair or relocation, and at least once every 12 months by an ASSE 5110 certified backflow technician.
Commercial RPZ Backflow Dumping Water in Broomfield?
Don’t let a failed RPZ backflow preventer flood your mechanical vault, destroy electrical equipment, or shut down commercial tenant operations. Our ASSE 5110 certified master plumbers deploy emergency differential testing, OEM rebuild kits, and 24/7 service.